AKCP-BASED ENVIRONMENTAL MONITORING · TEKNOANS
AKCP · SPECIAL-PURPOSE SENSORS

Tank Depth Sensor

The AKCP Tank Depth Sensor monitors fuel and liquid tank levels using hydrostatic pressure measurement.

20 mMaximum depth for water
15 mMaximum depth for gasoline
16,6 mMaximum depth for diesel
±%1 FSFull-scale accuracy
IP68Pressure probe protection rating
RJ-45AKCP sensor connection
15 mCAT5 communication cable
−20 / +80 °COperating Temperature

AKCP Tank Depth Sensor – Tank Level Monitoring

The AKCP Tank Depth Sensor (TDPS) monitors liquid levels in water and fuel tanks by measuring hydrostatic pressure. By defining the tank profile, the level can be displayed in litres or as a percentage.

The sensor is suspended by its cable near the bottom of the tank. Depth is calculated from the pressure of the liquid column above it. Nonlinear volume conversion is supported for different tank geometries.

In generator fuel tanks, it can be used to plan refills, detect sudden level drops and possible fuel theft, chart historical consumption and compare readings against fuel deliveries.

SNMP, email and SMS alarms (with a suitable modem) can be generated through sensorProbe+ and compatible securityProbe systems. AKCPro Server enables centralized monitoring.

Technical Specifications

Measurement Method
Hydrostatic pressure (liquid column pressure)
Supported Tank Depth
Water: 0–20 m (65 ft); gasoline: 0–15 m; diesel: 0–16.6 m
Calibration Options
Versions calibrated for maximum tank depths of 2 m, 5 m, 10 m or 15 m
Nonlinear Tank Support
Tank profiling / linearization for static liquid level
Measurement Distance and Accuracy
0.2% accuracy over a 0–2000 cm range for water
Full-Scale Accuracy
Up to ±1% FS
Mounting
Sensor probe is suspended inside the tank by its cable
Connection
RJ-45 jack; UFLS converter box with UTP CAT5 cable
Maximum Communication Cable
15 m (50 ft)
Included CAT5 Cable
15 ft (approximately 4.57 m) CAT5 LAN extension cable
Sensor Probe Cable
2 / 5 / 10 / 15 m depending on ordered version
Chemical Resistance
Gasoline, diesel and water
Operating Temperature
−20°C to +80°C
Protection Rating
Pressure sensor section: IP68
Module Power Supply
5 V via securityProbe5, E-Sensor8 or sensorProbe+
Sensor Probe Power Supply
12 V from an external power supply (included)
Compatible Units
securityProbe 5E, E-Sensor8 expansion module or sensorProbe+
Usage Limitations
Specific fuel types and fresh water; liquid compatibility must be verified for each application
Mounting Holes
30 mm diameter for sensor; four 5 mm holes for mounting plate
Mounting Hardware
M5 bolts and mounting plate; seal the perimeter with silicone

Information Document

AKCP Technical Datasheet (PDF)