Cabinet Analysis Sensor

Analyze cabinet thermal behavior and airflow from one location. Monitor front-to-rear temperature differences, humidity and differential pressure to identify hot spots and cooling issues.

AKCP Kabinet Analiz Sensörü
6× TemperatureFront/rear, top/middle/bottom measurement
3× ΔTFront-to-Rear Temperature Difference
2× HumidityRelative Humidity Measurement
1× ΔPDifferential pressure
±125 PaPressure Measurement Range
−40…+75 °CTemperature Measurement Range
0–100% RHHumidity Measurement Range
16 CabinetsMonitoring via a single IP address

Analyze Cabinet Thermal Performance and Airflow

The AKCP Cabinet Analysis Sensor (CAS) combines thermal mapping to identify cabinet hot spots with differential pressure measurements to evaluate airflow. With a sensorProbeX+ base unit, up to 16 cabinets can be monitored through a single IP address.

Differential Temperature (ΔT)

Thermal mapping uses six temperature measurement points at the top, middle and bottom of the front and rear of the cabinet, together with two humidity measurements. The front-to-rear temperature differences (ΔT) reveal thermal behavior throughout the cabinet.

Differential Pressure (ΔP)

For efficient cooling, pressure at the cabinet front should generally be higher than at the rear. CAS measures the front-to-rear pressure difference to help identify conditions that may cause unwanted mixing of hot- and cold-aisle air.

Rack Maps and Aisle Views

Quicklime Server can visualize Cabinet Analysis Sensor readings on rack maps. In data centers with hot- or cold-aisle containment, cross-sectional cabinet and aisle views help track temperature differences and airflow conditions.

Technical Specifications

Temperature Measurement
Temperature Sensor Readings
Six temperature sensor readings
Differential Temperature Readings
Three differential temperature readings
Measurement Range
−40 °C to +75 °C (−40 °F to +167 °F)
Measurement Resolution
In 0.1 °C / 0.2 °F increments
Measurement Accuracy
±0.3 °C at −40 °C, +25 °C and +75 °C; ±0.6 °F at the corresponding Fahrenheit values
Humidity Measurement
Humidity Sensor Readings
Two humidity sensor readings
Measurement Range
0–100% relative humidity (RH)
Resolution
1% RH increments; sensor reading resolution 0.01% RH
Accuracy at 25 °C
±%2 RH
Differential Pressure
Differential Pressure Reading
One differential pressure reading
Measurement Range
±125 Pa (±0,5 inH₂O / ±1,25 mbar)
Resolution
In 0.01 Pa increments
Accuracy at 25 °C
±%0,5
Connectivity and Hardware
Communication Cable
UTP CAT5e/6 cable via RJ-45 connection
Power Supply
Powered by sensorProbe+ series base units; no additional power supply required
Power Consumption
Typical 250 mW, 50 mA
Maximum Cable Length
18 m (60 ft) using standard CAT5/6 LAN cable
Dimensions
75 × 55 × 27 mm
Mounting
Desktop, wall, DIN-rail or magnetic mounting
Component Technology
Highly integrated, low-power surface-mount technology for long-term reliability
Operating Temperature
−35 °C to +80 °C
Operating Humidity
20–80% RH (non-condensing)
Number of Sensors
12
Compatibility and Important Notes
Compatibility
Compatible only with sensorProbe+ platform base units
Initial Connection / Update
On initial connection or after a sensorProbe+ update, the base unit may update the sensor firmware; the sensor may not be ready for immediate use
sensorProbeX+ Firmware Update
Sensor firmware can only be updated through the base unit's sensor ports
AKCP Technical Datasheet (PDF)