powerProbeX+
Revenue-grade energy monitoring for up to 48 individual circuits; single- or three-phase applications, three voltage inputs, 48 CT inputs, Modbus RS485 and BEB expansion support.


powerProbeX+ – Multi-Circuit Energy Monitoring and Energy Auditing
powerProbeX+ is a branch-circuit power monitoring device designed for revenue-grade measurement of up to 48 electrical circuits through a single IP address. It is suitable for per-customer or per-rack energy tracking in colocation data centers and for energy audits that identify the highest-consuming circuits in a facility.
Measurement of Up to 48 Circuits
The device has eight banks of six CT inputs, providing 48 current transformer inputs in total. Three voltage transformer inputs support single- or three-phase power monitoring. Voltage inputs are assigned to CT banks in software.
Elektriksel izolasyon
Mains voltage and high current do not enter the powerProbeX+ directly. External voltage and current transformers electrically isolate the device from the mains.
Key Features
Modbus and BEB Expansion
The Modbus RS485 port supports communication with third-party devices. Additional sensor ports, dry contacts, and mini relays can be added via the Basic Expansion Bus (BEB).
Independent IP-Based Monitoring
powerProbeX+ is a standalone device with its own IP address. It operates over 10/100 Ethernet and enables centralized monitoring of multiple circuits.
Colocation and Energy Auditing
Revenue-grade accuracy supports per-rack or per-customer energy tracking in colocation data centers and helps facilities identify circuits with high energy consumption.
Virtual Sensors and Integration
Each PPX+ includes ten free virtual sensors, expandable to 80 through licensing. Integration options are available for third-party Modbus/PMS devices and network services.
Notifications and Automation
Sensors can report status changes using four threshold levels. Alarms can depend on multiple sensor states and escalate in severity over time. Alerts can be sent by email, SMS, phone call (additional hardware required) or SNMP trap. Actions may include switching relays, waking or shutting down a remote server, uploading images/data by FTP and running custom scripts.
Heartbeat and False-Alarm Filtering
The Heartbeat Message feature can periodically report complete device and sensor status by email, SMS or SNMP trap; HTTP GET can transfer data to web servers. False-alarm filtering can limit events by time of day or day of week and restrict the number of alerts sent per hour.
Technical specifications
Technical specifications published on the AKCP powerProbeX+ product page.
| Boyut | 44 (W) × 44 (H), low-profile design |
|---|---|
| Montaj | Standart duvar montaj braketi; opsiyonel 1U rack; DIN ray braketi |
| Power | External 5.5 V 3 A adapter; 100–240 VAC / 0.22 A input; optional dual 12–24 or 40–60 VDC power inputs |
| Durum göstergeleri | Power and network status LED indicators |
| Operating Environment | 0°C–70°C; 20–80% RH, non-condensing |
| MTBF | 1,400,000 hours; based on sensorProbe+ field experience |
| Voltage Inputs | 3× voltage transformer inputs; compatible AKCP voltage transformers required |
| Current Inputs | 8 banks × 6 CTs = 48 CT inputs in total; compatible AKCP current transformers required |
| Phase Support | Single- or Three-Phase |
| Expansion Ports | EXP: EXP Remote Units or Modbus RS485; BEB: sensor-port, dry-contact and relay expansion |
| Maksimum sensör | Maximum 300 online sensors, including expansion units and virtual sensors |
| Sanal sensör | 10 free; up to 80 virtual sensors with licensing |
| 3. parti Modbus/PMS | Up to 4 Modbus devices, 15 sensors per device (license-dependent) |
| Desteklenen protokoller | Rsyslog · MQTT/MQTTS · SNMP v1/v2 · IPv6 · HTTPS · encrypted email; RADIUS/TACACS requires licensing |
| VPN | AKCPro Server connectivity via Ethernet or cellular network |
| Access Control User Database | 500 users with a UA license |
| Modbus Limit | For powerProbe+, a combined limit of 60 sensors applies to virtual sensors and Modbus devices over Modbus RS485 and Modbus TCP/IP |
48 devreyi tek cihazdan izleyin
Eight six-input CT banks monitor 48 current channels in total. Three voltage inputs are assigned to the relevant CT banks in software to calculate power and energy in single- or three-phase systems. External voltage and current transformers provide electrical isolation.
Colocation, Energy Auditing, and Multi-Circuit Power Monitoring
It can measure energy usage for individual customers or racks in colocation data centers, centrally monitor multiple circuits in distribution panels and identify high-consumption circuits during facility energy audits.
Let Us Size Your powerProbeX+ Project
We can help determine the right powerProbeX+ configuration based on circuit count, phase configuration, CT selection, voltage transformers, and expansion requirements.
powerProbeX+ Documents
Official AKCP product datasheet and 3D model links.