Measurement Range
Wet or dry
Sensor Type
On/Off contact input switch
Measurement Frequency
Multiple readings per second
Detection
Detects the presence or absence of water
Operating Temperature
−20 °C to +60 °C (4 °F to 140 °F)
Maximum Tensile Load
Must not exceed 50 lb
Minimum Bend Radius
2 inches (50 mm)
Pressure Warning
At 20 °C (68 °F), loads above 20 lb (9 kg) per linear inch may trigger an immediate alarm
Communication Cable
UTP Cat 5 cable connected to the sensor's RJ-45 socket
Base Unit Connection Cable
Up to 200 ft (60 m) from the RJ-45 intelligent sensor port using standard CAT5/6 LAN cable
Included Components
Water-sensing rope, non-sensing cable connecting the rope to the detection module, and main detection module
Water-Sensing Rope Length
Minimum 10 ft; custom lengths available up to 100 ft (30 m)
Non-Sensing Connection Cable
Standard 20 ft length
Power Supply
Powered by the controller; no additional power supply required
Automatic Detection
Full AutoSense support, including cable-disconnection alarms
Power Consumption
Typical 125 mW, 25 mA
Dimensions
56 × 55 × 33,3 mm
Mounting
DIN-rail or screw mounting
Important Notice
AKCP does not recommend placing the Rope Water Sensor on conductive surfaces