Integrate analog 4–20 mA transmitter signals into AKCP monitoring systems for remote monitoring, graphing and alarm threshold management of industrial and scientific sensors.
AKCP-PoweredPowered by the controller; no additional power supply required
LED StatusTwo LEDs for current detection and power status
15 m CableExtension up to 15 meters using standard CAT5e/6
DIN Rail / Screw MountingFlexible mounting options for field installation
Remote MonitoringGraphing, web interface, email and threshold/alarm management
4–20 mA Converter
The AKCP 4–20 mA Converter integrates third-party sensors with 4–20 mA transmitter outputs into the sensorProbe platform. The 4–20 mA standard is widely used in industry for reliable transmission of analog signals over long distances where electrical interference may be an issue.
Current signals are less susceptible to electrical noise than voltage signals. A voltage signal can be converted to current for long-distance transmission and then converted back to voltage for the AKCP monitoring unit to read. This approach is especially useful for collecting analog measurements from remote sensors in process control applications.
High-quality industrial sensors with 4–20 mA transmitters can take advantage of AKCP monitoring features, including graphing, browser-based monitoring, email notifications, thresholds and limit management.
Video could not be started. Please try again.
Technical Specifications
Input
2-pin Phoenix connector: 4–20 mA Iin(+) / Iin(-)
Output Voltage Range
+0,4 V – +2,0 V
Lineerlik
±0.09% of full scale, maximum
Accuracy
±0.15% of full scale (maximum ±0.3%)
Status Indicators
Current detection LED and power LED
Electrical Characteristics
Galvanik izolasyon yok
Operating Temperature
−35 °C – +80 °C
Operating Humidity
20–80% RH, non-condensing
Communication Cable
RJ-45 / UTP CAT5e/6
Power Supply
Powered by the controller; no additional supply required