AKCP-BASED ENVIRONMENTAL MONITORING · TEKNOANS
AKCP · POWER MONITORING SENSORS

4–20 mA Converter

Integrate analog 4–20 mA transmitter signals into AKCP monitoring systems for remote monitoring, graphing and alarm threshold management of industrial and scientific sensors.

AKCP 4-20mAmp Converter VC00 resmî ürün görseli
4–20 mA InputIndustrial current loop via 2-pin Phoenix connector
±0.09% LinearityMaximum linearity of ±0.09% of full scale
±0.15% AccuracyHigh-precision full-scale conversion
AKCP-PoweredPowered by the controller; no additional power supply required
LED StatusTwo LEDs for current detection and power status
15 m CableExtension up to 15 meters using standard CAT5e/6
DIN Rail / Screw MountingFlexible mounting options for field installation
Remote MonitoringGraphing, web interface, email and threshold/alarm management

4–20 mA Converter

The AKCP 4–20 mA Converter integrates third-party sensors with 4–20 mA transmitter outputs into the sensorProbe platform. The 4–20 mA standard is widely used in industry for reliable transmission of analog signals over long distances where electrical interference may be an issue.

Current signals are less susceptible to electrical noise than voltage signals. A voltage signal can be converted to current for long-distance transmission and then converted back to voltage for the AKCP monitoring unit to read. This approach is especially useful for collecting analog measurements from remote sensors in process control applications.

High-quality industrial sensors with 4–20 mA transmitters can take advantage of AKCP monitoring features, including graphing, browser-based monitoring, email notifications, thresholds and limit management.

Technical Specifications

Input2-pin Phoenix connector: 4–20 mA Iin(+) / Iin(-)
Output Voltage Range+0,4 V – +2,0 V
Lineerlik±0.09% of full scale, maximum
Accuracy±0.15% of full scale (maximum ±0.3%)
Status IndicatorsCurrent detection LED and power LED
Electrical CharacteristicsGalvanik izolasyon yok
Operating Temperature−35 °C – +80 °C
Operating Humidity20–80% RH, non-condensing
Communication CableRJ-45 / UTP CAT5e/6
Power SupplyPowered by the controller; no additional supply required
Power ConsumptionTipik 120 mW, 24 mA
Maximum Cable Length15 m / 50 ft
Dimensions65 × 62 × 15 mm
MountingDIN-rail or screw mounting
Number of Sensors1
AKCP Technical Datasheet (PDF)