Measurement / alarm state
Alarm or Normal
Sensor type
Dual-element passive infrared (PIR) sensor; high sensitivity
Maximum detection distance
3 m (listed as 9 ft in the AKCP source)
RFI immunity
High immunity to radio-frequency interference (RFI)
Daisy-chain connection
Up to 10 motion detectors on one intelligent sensor port
Operating Temperature
−20°C to +50°C (AKCP source gives 4°F–122°F; the lower-limit conversion is inconsistent)
Communication connection
RJ-45 socket; UTP CAT5 cable
Cable type
Approved low-capacitance shielded cable or UTP
Maximum cable length for one sensor
The AKCP page states “300 m (100 ft)”; the units are inconsistent and should be confirmed with the manufacturer.
Total cable length for a chain of 10 sensors
46 m (150 ft)
Maximum cable length between two sensors
Must be less than 6 m (20 ft)
Power Supply
Powered by the main controller; no additional power supply required
Auto detection
Full AutoSense support, including disconnection alarms
Power Consumption
Typically 50 mW; 10 mA
Dimensions
65 mm (W) × 62 mm (H) × 15 mm (D)
Mounting
Wall / ceiling mounting; DIN rail or screw mounting
Compatible controllers
AKCP sensorProbe+ and securityProbe series
Notification options
SMS, email or MMS through compatible securityProbe 5E; images from installed cameras can be attached to notifications